Two hardware suppliers have published the liquid-cooling and rack equipment they plan to show at Supercomputing 2026 (SC26) in Chicago. The exhibit floor at McCormick Place is open Nov. 17-19. The headline item comes from Delta Electronics: a coolant distribution unit (CDU) rated at 2.5 MW whose pumps run on 800 volts of direct current (VDC). Chatsworth Products (CPI) is showing a rack lineup built around the Open Compute Project's ORV3 specification. It also has two previews and a cabinet with integrated two-phase direct-to-chip cooling from ZutaCore.

Every figure below comes from the companies' own press releases, plus a secondary write-up on aicommission.org that restates Delta's announcement. Both releases are product announcements for a trade show. Neither names a customer, a deployment site or a ship date, and none of the performance numbers has been checked by an outside party.

The 800 VDC CDU

Delta's release is dated Nov. 13 and was distributed through HPCwire's Off the Wire section. It describes an "800 VDC 2.5 MW In-Row L2L CDU." L2L means liquid-to-liquid: the unit moves heat from the coolant loop serving the IT equipment to the facility's water loop. According to Delta, the unit uses three hot-swappable 25 kW pumps that run on 800 VDC. They are arranged in a 3+0 configuration, which Delta describes as delivering zero-downtime operation, and the unit can move up to 3,850 liters per minute (LPM) at 60 psi.

Two details stand out to anyone sizing a cooling plant:

  • Power input. Delta built this CDU's pumps for 800 VDC. Its release also describes a booth exhibition area covering 800 VDC and ±400 VDC cooling. A secondary write-up on aicommission.org goes further and says the CDU itself is designed to run from both 800 VDC and ±400 VDC facility architectures. The Delta release as read for this report does not make that statement about the CDU, so readers should treat it as unconfirmed until Delta's own materials or a third party confirm it.
  • Redundancy. In a 3+0 arrangement, the "+0" conventionally means no spare pump is held in reserve, so all three pumps would be needed for the rated performance. That is DataCenterFeed's reading of the notation, not a statement from Delta. Cooling designs are often specified with N+1 pump redundancy. The release does not say how the unit behaves if one pump fails or is being swapped. The pumps are hot-swappable, meaning they can be replaced while the unit runs.

The release does not say whether the CDU is available now, what it costs, or whether anyone has ordered it. The aicommission.org write-up says commercial shipments are slated for early 2027, but it does not attribute that to Delta's release and DataCenterFeed could not confirm it.

Cooling the Power Hardware, Not Just the Chips

Delta is also debuting what it calls a Power Shelf Embedded Cold Plate. The release describes it as customizable and ultra-thin, with flexible manifold layouts and multi-channel flow paths for hotspots in power systems. In other words, it puts liquid cooling into the rack power shelf that converts and distributes power, rather than only onto processors.

The release also describes a Vertical Power Delivery (VPD) double-sided cooling solution for Open Adapter Card architectures. In vertical power delivery, power-conversion components sit directly beneath the processor rather than beside it on the board. Delta says its design cools up to 3,000 W of computing components and 500 W of power components in a 40 mm cold plate, with heat flux above 170 W/cm². Heat flux is the amount of heat leaving each square centimeter of surface, and it is a common gauge of how hard a cold plate is being pushed. Delta is also showing a hot-swappable cold plate with a modular design for stacked solid-state drives (SSDs).

The Rest of Delta's Cooling Lineup

According to Delta's release, the booth will also include several products at other sizes:

  • A 4U in-rack CDU rated up to 200 kW.
  • An open in-row CDU built for Project Deschutes, rated up to 2 MW at a 3 °C approach temperature. Approach temperature is the gap between the temperature of the facility water supply and that of the coolant delivered to the IT loop.
  • A rack-mounted liquid-to-air CDU for Google's OCP Project Brazos, rated up to 60 kW per rack in a closed loop. A liquid-to-air unit lets a liquid-cooled rack reject its heat into room air, which aicommission.org describes as an option for facilities without hydronic (water-loop) infrastructure.
  • A next-generation fan wall that uses 450 mm EC (electronically commutated) blowers.

The release includes a statement from Martin Tsai, general manager of the Fans and Thermal Management Business Group at Delta Electronics. Delta will be at booth #1443.

Chatsworth's Racks, Busbars and Previews

Chatsworth Products' release is dated Nov. 10 and went out through PR Newswire. It centers on rack structure and power distribution, with cooling as a second focus. CPI will be at booth #4203. The company lists the conference as running Nov. 15-20, with exhibits Nov. 17-19.

CPI says it will show OCP Accepted ORV3 racks in standard and customer-specific 44OU and 48OU configurations and in High-Power Rack configurations. The racks support 21-inch Open Rack equipment, with optional support for 19-inch EIA equipment. On power, the company lists optional 48V DC power shelves ranging from 18 to 33 kW and compatible busbars ranging from 350 A to 2,500 A. A busbar is the rigid conductor that carries power up and down the rack.

CPI also has two previews, products it is showing but describing in less detail:

  • eConnect PDUs with 480V input. CPI says these power distribution units are designed to support higher rack-level power requirements. The release does not give capacity or availability figures for these units.
  • CoolStream Rear Door Heat Exchanger. CPI describes it as designed to bring liquid-assisted cooling to the rack level. A rear-door heat exchanger is a liquid-cooled coil mounted on the back of the rack that removes heat from exhaust air before it reaches the room. The release gives no capacity figures.

CPI is also showing ZutaCore's HyperCool system integrated into its ZetaFrame cabinet. CPI describes HyperCool as waterless, two-phase direct-to-chip liquid cooling. In two-phase cooling, a dielectric fluid boils at the cold plate and condenses elsewhere, so no water runs to the processor. The release includes a statement from Sam Rodriguez, senior product manager at Chatsworth.

How to Read These Announcements

These are trade-show product releases. They tell readers what two suppliers want to put in front of AI and high-performance computing (HPC) buyers, and how those suppliers rate their own equipment. They do not show adoption. Neither company names a data center, operator or customer using the products. Neither says whether the flow rates, megawatt ratings or heat-flux numbers have been measured independently.

The aicommission.org article published Nov. 16 is consistent with Delta's release on the main CDU specifications: the 2.5 MW rating, the three 25 kW pumps, 3,850 LPM at 60 psi, the 2 MW Deschutes unit, the 60 kW Brazos unit, the 200 kW in-rack CDU and the 3,000 W and 500 W figures for the vertical power delivery cold plate. It also states a 3,000 W figure for the power shelf cold plate, which does not appear in the Delta release as read for this report. It adds no testing of its own, and parts of its framing are editorial. DataCenterFeed treats it as a restatement of Delta's announcement, not independent confirmation.

For utilities, local officials and residents following proposed campuses, these products are not tied to any specific project. They are an indication of what suppliers are offering to AI and HPC buyers: CDUs rated in megawatts, liquid cooling for rack power shelves, and cooling pumps designed for 800 VDC.

What Happens Next

The SC26 exhibit floor at McCormick Place in Chicago opens Nov. 17 and runs through Nov. 19. Delta will show the 800 VDC CDU and the rest of its lineup at booth #1443. Chatsworth Products will show its ORV3 racks, its eConnect and CoolStream previews, and the ZutaCore-equipped ZetaFrame cabinet at booth #4203. Neither release gives a commercial availability date, pricing or a customer deployment for the products it describes.