Many operators want to run dense GPU hardware in buildings that were designed for air cooling. Nexalus and RENDA have announced a product aimed at that problem: the RENDA Nova8, a 4U server with self-contained liquid cooling. According to the companies' Nov. 17 Business Wire release, it holds eight Nvidia RTX PRO 6000 Blackwell GPUs running at their full 600 W each, plus a CPU.
The pitch is simple. The cooling loop stays inside the chassis. According to DEVELOP3D's Nov. 18 report, the server fits a standard 19-inch air-cooled rack, and the companies say it needs no added facility piping. An independent technical write-up from StorageReview on Nov. 23 adds a caveat that matters for facility planners: unless optional water connections are used, the heat ends up in the room.
The performance and efficiency numbers below are vendor claims or vendor-run tests. The companies say they will offer a remote Test Drive so vetted prospects can check them.
What the Companies Say They Built
The release describes the Nova8 as co-developed and jointly patented by the two companies. Nexalus supplies the cooling, which uses jet-impingement cold plates, and RENDA builds the server. RENDA's product page describes eight full-power RTX PRO 6000 Blackwell GPUs in one 4U server, "liquid-cooled end-to-end by Nexalus."
DEVELOP3D reports that each of the eight GPUs carries 96 GB of memory and runs at 600 W in a single-slot form factor. The release says the GPUs run more than 20 C below their maximum rated temperature.
For redundancy, the release lists 10 pumps and 16 fans. StorageReview gives more detail. It says ten micropumps run through five redundant loops, the 16 fans are set up in push-pull pairs, and the system uses quick-disconnect fittings.
The release says UNICOM Engineering will handle after-sales support. The release says the companies will showcase the system at Data Centre World Paris on Nov. 18-19.
The Performance Claims, and How They Were Measured
The headline figures come from the companies' internal testing, as reported in the release and by DEVELOP3D:
- 55,000 tokens per second on a Llama 3.3 benchmark. The companies describe this as up to 20 percent more throughput than comparable air-cooled systems.
- 8.6 tokens per watt. The companies describe this as up to 22 percent greater energy efficiency than comparable air-cooled systems.
RENDA's product page repeats the "up to 55,000 tokens per second" claim. The release and DEVELOP3D do not name the air-cooled systems used for comparison. StorageReview reports that RENDA's reference is a published result of 45,527 tokens per second and 7.03 tokens per watt from a tier-one air-cooled server with eight RTX PRO 6000 Blackwell Server Edition GPUs, whereas the Nova8 test used Workstation Edition cards. That reference ran two EPYC CPUs, two replicas per GPU and 8,192 concurrent users, so StorageReview notes the two results come from different serving configurations.
StorageReview describes the test setup that RENDA used. The workload was Llama 3.3 70B Instruct quantized to NVFP4 and served on TensorRT-LLM. With one replica per GPU, each replica handled 512 concurrent requests, with 256 input tokens and 256 output tokens per request. Under that setup, StorageReview reports that the best tuned run reached 54,564 tokens per second, and a one-hour run averaged 53,984, against the companies' "up to 55,000" headline. StorageReview notes these are vendor results that it did not run or audit.
Short prompts and short responses at high concurrency are one specific kind of inference workload. Results can differ with longer contexts, other models or other serving software. The sources do not include results for those cases.
StorageReview also notes a gap that operators will care about given the redundancy pitch. The companies have not published throughput figures with a pump or fan failed. So the sources do not show whether, or how much, the GPUs slow down when part of the redundant cooling is lost.
Where the Heat Goes
The "drop-in" claim needs the most careful reading on this point. Liquid cooling inside the chassis moves heat away from the GPUs. It does not remove that heat from the building on its own.
StorageReview reports that RENDA lists optional rear quick-connects that can carry heat out as water at up to 60 C. Without them, the server's internal radiator releases heat into the room, and StorageReview says the existing air handling then has to absorb the full load.
That leaves two ways to deploy the system:
- Air-rejection mode. The server needs no facility water, which matches the companies' "no added facility piping" description. But the room's cooling system takes all of the heat from eight 600 W GPUs plus a CPU in one 4U slot. Whether a given air-cooled room and rack can handle that load is a site-by-site question that the sources do not address.
- Water-export mode. The rear quick-connects send heat out as water at up to 60 C, according to StorageReview. That takes the load off the room's air handling, but the facility needs water connections to receive it.
In other words, the product changes where the GPUs' heat is collected. In its no-piping mode, it does not reduce the amount of heat the building has to remove.
Who This Is Aimed At
The release title calls the Nova8 a server "for data center retrofits." DEVELOP3D's main point about fit is that the chassis goes into a standard 19-inch air-cooled rack. That would appeal to an enterprise or colocation customer who wants dense Blackwell-generation inference hardware without first adding liquid-cooling infrastructure to the facility.
StorageReview says neither company has disclosed pricing or a shipping schedule, or published inlet temperature limits, airflow requirements, dimensions or weight. It cites a RENDA estimate of about 6.4 kW typical system power at full load, and notes that three such servers in one rack would come to roughly 19 kW in 12U, which it says is more than many air-cooled rows are typically provisioned to remove.
What Happens Next
The step the companies have put on the record is evaluation. According to the release and DEVELOP3D, Nexalus and RENDA are offering a remote Test Drive, with access granted to vetted prospects, who can run their own models on the system before buying. The release also says qualified organizations can pre-order. The release says UNICOM Engineering will provide after-sales support for systems that ship. None of the sources gives a shipping date or pricing, and the companies have not published a figure for throughput with a pump or fan failed.