Vertiv has added two products to its 800-volt direct-current (800 VDC) power line for AI data centers. According to Unite.AI, the company introduced them on Nov. 17, 2026. The PowerDirect 9000 is a 1.5-MW power center that feeds a row or pod. The PowerNexus MV SST is a 5-MW solid-state transformer that converts medium-voltage utility power directly to 800 VDC for a data hall. DatacenterDynamics reported the expansion on Nov. 26.
The two new products join the PowerDirect 5000 power rack Vertiv announced in May and the PowerDirect 3000, an in-rack DC-DC shelf. Together, the four cover conversion points from inside the rack to the data hall's medium-voltage connection. All figures in this article are Vertiv's own claims, as reported by the outlets cited. DataCenterFeed could not read Vertiv's own release page.
Where the AC-to-DC conversion happens
In conventional AC designs, power travels through the building as AC and is converted to DC inside each server's power supply. In 800 VDC designs, that conversion happens earlier, and power travels to the racks at high-voltage DC. That leaves an engineering choice about where the conversion point sits.
Unite.AI describes Vertiv's portfolio as giving operators three places to set the AC-to-DC boundary: beside an IT rack, ahead of a pod, or at the data hall's medium-voltage connection. Vertiv does not present DC as a replacement for AC across the board. According to Unite.AI, the company expects AC and DC architectures to coexist and does not expect a single adoption timetable. Unite.AI adds that the portfolio is meant to let 800 VDC be introduced without committing an entire facility to one design.
The four products, from rack to grid
PowerDirect 3000: inside the rack
The PowerDirect 3000 sits inside compute racks. It steps 800 VDC down to the 54 VDC used by compute trays. DCD reports that it is rated at 90 kW with a peak efficiency of 98.5%. Unite.AI describes it as a 1U shelf with the same 90-kW rating and 98.5% peak efficiency. It adds that the shelf delivers 180% pulse power for 0.5 milliseconds in Vertiv's specifications.
According to DCD, deploying the conversion equipment outside the IT racks frees 8 to 16 rack units for additional computing equipment and lets operators keep existing AC infrastructure without a complete redesign.
PowerDirect 5000: beside the rack
The PowerDirect 5000 power rack, announced in May, sits next to the IT rack. DCD reports that it takes 480 VAC and delivers either 800 VDC or ±400 VDC. It holds 30 hot-pluggable 30-kW power supply units plus an integrated battery backup unit designed for at least 50 seconds of hold-up time. Unite.AI says Vertiv rates the unit at up to 800 kW. Data Phoenix says the company describes it as configurable up to 800 kW.
PowerDirect 9000: ahead of a pod
The PowerDirect 9000 is one of the two new products. It moves the conversion point upstream so that one unit can serve a whole row or pod. Unite.AI reports that it converts 480 VAC to 800 VDC, is rated by Vertiv at 1.5 MW and scales in 60-kW increments through 27 hot-pluggable power supply units. Power reaches the racks over Vertiv's PowerBar Track DC busway, with a metered, breaker-protected drop at every rack. DCD likewise describes distribution through DC busways and tap-off boxes.
Backup power comes from a separate product. DCD reports that the PowerDirect 9000 can connect to the EnergyCore Li5 800 VDC battery cabinet, with each cabinet able to provide 200 kW of backup. Unite.AI says Vertiv rates each cabinet at 200 kW of continuous backup and up to 98% conversion efficiency.
PowerNexus MV SST: at the medium-voltage connection
The second new product goes furthest upstream. According to DCD, the PowerNexus MV SST is a 5-MW solid-state transformer that converts medium-voltage AC directly to 800 VDC in a single stage. It is containerized, liquid-cooled and designed to sit outside the data center facility. Unite.AI says the outdoor container is rated by Vertiv at up to 98% AC-to-DC efficiency and eliminates two to three intermediate conversion steps found in conventional power trains. Vertiv's product brief, as described by Data Phoenix, describes a 13.8 kV AC input configuration that uses power electronics for conversion and a medium-frequency transformer to electrically isolate the input from the output.
DCD reports that Vertiv claims the system supports bidirectional power flow. According to Data Phoenix, one unit can serve Vertiv's 4.8 MW reference design. The listed safety features for the portfolio are touch-proof busbars, high-voltage isolation, midpoint grounding and ground-fault detection, and Unite.AI also lists arc-flash prevention.
How the pieces fit together
Read together, the ratings show a step up in scale at each level: 90 kW per in-rack shelf, up to 800 kW per sidecar power rack, 1.5 MW per pod power center and 5 MW per medium-voltage transformer, as the sources report them. An operator could convert beside the rack and keep AC infrastructure upstream, or convert at the hall's medium-voltage connection and feed a DC busway. Both Unite.AI and Data Phoenix describe the PowerDirect 3000 shelf as the final step down to 54 VDC in the pod-level design.
DCD's coverage includes comments from Scott Armul, Vertiv's chief product and technology officer, and Kyle Keeper, senior vice president of Vertiv's power management business unit.
A crowded medium-voltage field
Vertiv is not alone in the grid-facing end of this market. DCD notes that GE Vernova, Tesla and On.energy have launched similar products in recent months; DCD's sentence refers to medium-voltage UPS products for the data center market. The reports do not compare specifications across those vendors, and DataCenterFeed has not independently compared them.
What is not yet known
The announcement leaves several practical questions open. Data Phoenix reports that the announcement gave no commercial availability date and named no production installation for either new system. The coverage DataCenterFeed read gives no pricing, no lead times and no independent efficiency testing. The bidirectional power flow claimed for the PowerNexus MV SST is described only as a Vertiv claim. Unite.AI says, according to Vertiv, that it can improve grid power quality and provide active power support, but the sources do not say how it would be used on a specific site.
For utilities and local officials, the medium-voltage unit sits at the point where a campus connects to the distribution system. The sources do not describe any interconnection filings, utility partnerships or site permits involving the product.
What Happens Next
According to Data Phoenix, Vertiv reports ongoing pilots and technical validation across its 800 VDC portfolio. Unite.AI adds that Vertiv showed the portfolio at SC26 from Nov. 17 to 22, 2026, with customer-specific collaborative development underway. The company has not announced a commercial availability date or named a production installation for the PowerDirect 9000 or the PowerNexus MV SST, and the sources list no further scheduled milestone. Unite.AI reports that Vertiv expects AC and DC architectures to coexist and has given no single timetable for adoption.